System Alarms / Warning Messages

Type in the search boxes to locate the desired fault code.

Number HMI Message PLC Message Remedy
Number HMI Message PLC Message Remedy
001 FLT_SysLv1[0].0_CONTROL POWER OFF.i10114 OFF. CONTROL POWER OFF Place Control Power Disconnect Switch to ON position.
002 FLT_SysLv1[0].4_E-STOP PB PRESSED.(HMI)si10400/01 OFF. E-STOP PB PRESSED.(HMI) Reset E-Stop and perform fault reset.
003 FLT_SysLv1[0].12_SAFETY GATE OPENED.si10600 OFF SAFETY GATE OPENED Close and Latch Safety Gate
004 FLT_SysLv1[0].20_LIGHT CURTAIN 1 BLOCKED.I_x.xx OFF. LIGHT CURTAIN BLOCKED Remove Object Blocking Light Curtain
005 FLT_SysLv1[0].28_PLC FAULT.2 PLC FAULT View PLC Status Screen and Rectify the Fault
006 FLT_SysLv1[0].31_AIR PRESSURE LOW.i40600 AIR PRESSURE LOW Adjust Air Pressure on Stand to Required Pressure
007 FLT_SysLv1[0].30_DRY CYCLE FAULT. (PART DETECTED) DRY CYCLE FAULT - PART DETECTED Remove Part and resume automation
008 FLT_SysLv1[0].8 CIRCUIT BREAKER TRIPPED.i10106 OFF. CIRCUIT BREAKER TRIPPED Reset Circuit Breaker
009 FLT_SysLv1[0].42 TURNTABLE INDEX FAULT TURNTABLE FAILED TO INDEX Verify all objects blocking the turntable are removed from work area.
010 FLT_SysLv1[0].29_ETHERNET IP SYSTEM FAULT. EHTERNET IP SYSTEM FAULT Visually inspect all EtherNet Modules, verify all connections are secured.